| You are here: Topics › Standard AMF Panel Specification |
|
| 160 - 380 KVA | 500 - 625 KVA | 750 - 2000 KVA| 15 - 140 KVA |
|
|
|
Specification for STD
AMF Panel Spect. No. A-01 750 – 2000 KVA
Switch Gears:
›Suitably
rated Electrically operated drawout type 4 pole ACB for Alternator
›Suitably rated Electrically operated
drawout type 4 pole ACB for MAINS
|
|
Microprocessor Based AMF Module
Incorporating:
| |
Functions |
|
|
|
| |
|
› |
Supply Failure Timer |
| |
|
› |
Restoration Timer |
| |
|
› |
Impulse automatic engine Start / Stop logic & engine
fails to start lockout |
| |
|
› |
Generator Voltage, Current & Frequency Monitoring. |
| |
|
› |
Battery Voltage Sensing & Monitoring. |
| |
|
|
| |
Selector Switches & Push Buttons |
| |
|
› |
Manual / Auto / Test Selector Switch. |
| |
|
› |
Engine START / STOP |
| |
|
|
|
| |
Metering |
| |
|
› |
Indication for Volt, Current, Frequency |
| |
|
|
|
| |
Annunciation (LED TYPE) |
| Faults |
Alarm |
Trip |
LED Ann. |
| Engine Fails to Start |
|
|
|
| Low Lube Oil Pressure |
|
|
|
| High water temperature |
|
|
|
| Generator Overload |
|
|
|
| Battery Voltage |
|
|
|
| Low Fuel Level (OPTIONAL) |
|
|
|
|
Additional
Features:
Metering :
›Continuous reading Digital Voltmeter / Ammeter / Frequency meter
›Continuous reading Digital KW / Power Factor / KVA or KVAR meter
›Electronic (with counter display) KWH Meter
RPM Meter & Running-hour meter
›Ammeter & Voltmeter for field excitation.
Relay :
›IDMT 2Over current
& 1Earth Fault Relay
›Earth Fault Relay, CDG 11 / EEFR
(OPTIONAL)
›Earth Leakage Relay (OPTIONAL)
Indications (LED) :
›DG ON , Load on DG
›Mains ON, Load on Mains
›O/C & E/F
trip.
Push Buttons (AMF MODULE
BY PASS MODE) :
›Fault ACCEPT / RESET
Engine Meters for
›Lub Oil Pressure
›Water Temperature
|
Battery Charger:
›SMPS Based automatic Float
cum Boost Battery Charger with :
›DC Voltmeter & Ammeter
›Selector Switch for Auto / Manual & Float / Boost.
|
|
|
|
|
|
| |
|
|
|