Powerica
Power Distribution System

62.5 KVA

SPECIFICATION FOR STANDARD AMF PANEL 62.5 KVA

Cubicle type, base mounting control panel with hinged doors, undrilled bottom gland plate, AL. Bus Bar and accommodating the following:

SWITCH GEARS:

  • 100A, 4 Pole Contactor for ALTERNATOR with Thermal O/L relay
  • 100A, 4 Pole Contactor for MAINS (OPTIONAL)

BACK-UP PROTECTION:
MCCB for short circuit protection

MICROPROCESSOR BASED AMF MODULE INCORPORATING:

Functions:
Supply Failure Timer
Restoration Timer
3 Impulse automatic engine Start / Stop logic
Mains / Generator Voltage & Frequency Sensing

Multifunction Meter & PCC 0301 with Scrolling Readings for

  • Water Temperature/ Lube Oil Pressure
  • Voltage / Ampere/ Frequency / kW / kVA
  • Running-hour counter

Fault Indication (LED Type)

  • Over / Under Speed
  • Fails To Start
  • Low Oil pressure
  • Battery Charger Failure
  • High Engine Temperature

Electronic kWH meter (Counter Display)

Current Transformers

Indications (LED):
DG ON, Load on DG
Mains ON, Load on Mains, Battery Charger ON

Push Buttons (AMF MODULE BY PASS MODE)

  • Engine START / STOP ( Provided on Engine Controller )
  • Generator Contactor CLOSE / TRIP
  • Mains Contactor CLOSE / TRIP (If provided)
  • Fault ACCEPT / RESET

BATTERY CHARGER:
SMPS Based Unit with inbuilt Auto/Manual & Float/Boost Facility
DC Voltmeter & Ammeter (Separate)

PLHO / 0712/RKS/ASN