SPECIFICATION FOR STANDARD GCU PANEL 320-380kVA
Cubicle type, floor mounting control panel with hinged doors, un-drilled bottom gland plate, AL. Bus Bar and accommodating the following:
SWITCH GEARS: 800A, 3 Pole ACB EDO Type with 110A, 3P neutral contactor for ALTERNATOR
 
ADDITIONAL FEATURES:
Metering:
Combined Meter for Voltage / Ampere / Frequency
Combined Meter for kW / Power Factor / kVA
Electronic kWH Meter (Counter Display)
Current Transformers
 
Relay:
Earth Fault Relay (Electronic type)
 
Indications (LED):
DG ON, Load on DG, Neutral Contactor ON, DC Supply ON,
DG Common Warning, DG Common Shutdown, Mains ON, Battery Charger ON
 
Push Buttons (GCU BY PASS MODE):
Engine START / STOP
Generator Breaker CLOSE / TRIP
Fault ACCEPT / RESET
 
BATTERY CHARGER: (Applicable for AMF Panel only)
SMPS Based Unit with inbuilt Auto/Manual & Float/Boost Facility
DC Voltmeter & Ammeter (Separate)
 
Microprocessor Based Generator Control Unit (GCU) with following features:
Metering
For Alternator
Electrical metering digital - A, V, Hz, PF, kW, kVA, kVAR, kWH
For Bus / Mains
Electrical metering digital - V, Hz, & THD
Other features
Electrical metering digital - Bat V, Engine RPM, Engine Running Hour
2. Protection
U/V, O/V, U/F, O/F, RPR, RKVR, O/C, loss of Excitation
External protection - Discrete input
3. 16 faults display on GCU LCD Screen.
4. Integrated Automation functions/sequences, through GCU
Auto start & stop
Auto Synchronising
Auto Load Sharing - kW & kVAR
 
PLHO / 0712/RKS/ASN