| SPECIFICATION
FOR STANDARD GCU PANEL 320-380kVA |
|
|
| Cubicle
type, floor mounting control
panel with hinged doors, un-drilled
bottom gland plate, AL. Bus
Bar and accommodating the following: |
| › |
|
SWITCH
GEARS: 800A, 3 Pole ACB
EDO Type with 110A, 3P
neutral contactor for
ALTERNATOR |
|
| |
| ADDITIONAL
FEATURES: |
| Metering: |
| Combined
Meter for Voltage / Ampere /
Frequency |
| Combined
Meter for kW / Power Factor
/ kVA |
| Electronic
kWH Meter (Counter Display) |
| Current
Transformers |
| |
|
| Relay: |
|
Earth Fault Relay (Electronic type) |
| |
| Indications
(LED): |
| DG
ON, Load on DG, Neutral Contactor
ON, DC Supply ON, |
| DG
Common Warning, DG Common Shutdown,
Mains ON, Battery Charger ON |
| |
| Push
Buttons (GCU BY PASS MODE): |
| › |
|
Engine
START / STOP |
| › |
|
Generator
Breaker CLOSE / TRIP |
| › |
|
Fault
ACCEPT / RESET |
|
| |
| BATTERY
CHARGER: (Applicable for AMF Panel
only) |
| SMPS
Based Unit with inbuilt Auto/Manual
& Float/Boost Facility |
| DC
Voltmeter & Ammeter (Separate) |
| |
| Microprocessor
Based Generator Control Unit (GCU)
with following features: |
| Metering |
| For
Alternator |
| › |
|
Electrical
metering digital - A, V, Hz,
PF, kW, kVA, kVAR, kWH |
|
| For
Bus / Mains |
| › |
|
Electrical
metering digital - V, Hz, &
THD |
|
| Other
features |
| › |
|
Electrical
metering digital - Bat V, Engine
RPM, Engine Running Hour |
|
| 2.
Protection |
| › |
|
U/V,
O/V, U/F, O/F, RPR, RKVR, O/C,
loss of Excitation |
| › |
|
External
protection - Discrete input |
|
| 3.
16 faults display on GCU LCD Screen. |
| 4.
Integrated Automation functions/sequences,
through GCU |
| › |
|
Auto
start & stop |
| › |
|
Auto
Synchronising |
| › |
|
Auto
Load Sharing - kW & kVAR |
|
| |
| PLHO